Midea Air Conditioning Fault Code List
1. Split Wall-mounted Air Conditioner
1, 25, 5F, F1 series split machine
Work light timer light defrost light indication content
〇〇× Current protection (PRI-5MI PRI-SEC)
☆ ☆ × Fan speed runaway
☆ 〇× Zero-crossing detection error
☆ ☆ × The main chip and computer cannot communicate
☆ 〇× Indoor evaporator temperature sensor is open or short circuit
☆ × × Indoor room temperature sensor is open circuit or short circuit
〇☆ × Thermal fuse disconnection protection (FUSED)
☆ 〇× Indoor evaporator high temperature protection or low temperature protection
☆ × × Dehumidification mode indoor temperature is too low protection
× 〇〇 Power on Error in writing EEPROM parameters during operation
〇〇〇 Error in reading EEPROM parameters when power on
〇× ☆ Error in writing EEPROM parameters during running
〇 (on) ☆ (flashing) × (off)
2. Qingxingxing 26, C series split machine
Running light, timing light, automatic ventilation light, continuous ventilation light, defrost light indication content
1HZ just powered on but not turned on
5HZ 5HZ 5HZ The motor is out of control, no feedback Signal
5HZ Indoor sensor detection port is abnormal
5HZ Evaporator sensor detection port is abnormal
5HZ 5HZ 5HZ 5HZ Thermal fuse is blown
0.1HZ 0.1HZ 0.1HZ 0.1HZ. 0.1HZ No zero-crossing signal
, Qingjingxing 26, C1 series split unit
Code indication content
P0 4 consecutive current protection
P1 Indoor fan speed out of control
P2 Indoor board and switch board can not communicate within 2 minutes
P Indoor evaporator temperature sensor open circuit or short circuit
P4 Indoor room temperature sensor open circuit or short circuit
P5 Indoor fan temperature fuse disconnected
P6 Zero-cross detection fault
P7 Model selection error
4. Starlight type (26A, 2A, 6A, 4A) series split machine
Starlight type (2, 26, 2I1) series, 22Y series split machine
Work light timing light defrosting light indication content and LED status
☆ × ☆ Four times current protection 5HZ
☆ × × Fan speed runaway 5HZ
☆ ☆ ☆ Zero-crossing detection error 0.1HZ
☆ ☆ 〇The main chip and the computer cannot communicate at 5HZ
× × ☆ Indoor evaporator temperature sensor open circuit or short circuit 5HZ
× ☆ × Indoor room temperature sensor open circuit or short circuit 5HZ
☆ ☆ × Thermal fuse disconnection protection 5HZ
〇〇〇Error reading EEPROM parameters when power on
(When judging the fault, only use the three lights listed above to judge the status of other lights)
5. Star color type (50A, 60A, 70A) series split machine
Type indication content LED status remarks
Protect the current protection running light, timer light, defrost light (only air supply light) flashing at 5Hz at the same time within 10 minutes after the compressor is turned on for four consecutive times. p> The abnormal timing light of the faulty room temperature sensor detection port flashes at 5Hz and automatically recovers after the fault is cleared
J v V m l ? J The abnormal operation light of the fault evaporator sensor detection port flashes at 5Hz
The faulty condenser sensor detection port is abnormal Frost light flashes at 5Hz
MalfunctionEEPROM communication error (reserved) Running light and timing light flash at 5Hz
6. I-type series split machine KF(R)-2GWIY
Working light, automatic light, timing light, defrost light indication content
〇☆ 〇× Current protection
☆ ☆ ☆ × Fan speed out of control
☆ ☆ 〇× Zero-crossing detection error|
☆ 〇☆ × Main chip and computer cannot communicate
☆ 〇〇× Indoor evaporator Temperature sensor open circuit or short circuit
☆ 〇× × Indoor room temperature sensor open circuit or short circuit
〇☆ ☆ × Thermal fuse disconnection protection
☆ × 〇× Indoor evaporator high temperature protection or low temperature protection
☆ × × × Protection against low indoor temperature in dehumidification mode
☆ 〇〇〇Error writing E2PROM parameters when power on
〇〇〇〇Error reading E2PROM parameters when powering on
〇× × ☆ Read and write during operation E2PROM parameter error
7. H-type series split machine
KF(R)-25GWHY
Fresh light timing light working light indication content
☆ ☆ ☆ Current protection
☆ ☆ 〇Fan speed Out of control
☆ 〇☆ Zero-crossing detection error
〇〇☆ Indoor evaporator temperature sensor open circuit or short circuit
☆ 〇〇 Indoor room temperature sensor open circuit or short circuit
8. Three-horsepower series large split machine:
KF(R)-60GWY
KF(R)-70GWY
KF(R)-70GWSY
Type Indication Content LED Status Remarks
Protection Occurs Four Times in One Hour Compressor Overcurrent protection running light, timer light, defrost light flashes at 5HZ Protection (phase loss, phase sequence and exhaust temperature protection) All lights flash at 5HZ
The fault room temperature sensor detection port is abnormal and the timing light flashes at 5HZ Automatic recovery after the fault is cleared
The fault evaporator sensor detection port is abnormal and the automatic light is 5HZ Flashing
Abnormal defrost light of fault condenser sensor detection port flashes at 5HZ
Fault temperature fuse blown running light and timing light flashes at 5HZ
9. Split machine after the main chip is unified:
KF( R)-2GWY KF(R)-262GW(D)Y KF(R)-252WY
KF(R)-64GWY KF(R)-25GWEY KF(R)-28GWEY
KF(R)-5GWY KF(R)-26GWCY KF(R)-GWCY
Run light setting Hourly light, automatic light, defrost light indication content
☆ × × × The indoor fan speed is out of control for more than 1 minute
(with a ventilation light, the ventilation light also flashes)
× ☆ × × The room temperature sensor is open or short circuit
× × ☆ × Evaporator sensor open circuit or short circuit
☆ ☆ × × Thermal fuse blown (with ventilation light,
ventilation light also flashes)
☆ ☆ ☆ ☆ No fault Zero signal (all lights flash at 0.1HZ)
10. Midea-Toshiba series split machine:
KF (C)-6 (4, 45) GWY KFR-2 (6) GWY
KFR- 4(45) GWY
Indoor code situation table:
LED status indication content
Running light 1HZ flashes at first power on and normal standby
Running light flashes at 5HZ immediately after power-on The room temperature sensor or evaporator sensor is open circuit Or short circuit
After power on, the running light flashes at 5HZ for one minute, and the speed of the indoor fan is out of control
The running light and timing light flash at 5HZ The thermal fuse is open
Running light, timing light, defrost light (or only air supply light) flashes at 5HZ
1. The compressor connection is not well connected, the compressor overcurrent protector is open or the electric control is broken
2. The power supply voltage is too low
. Electric control parts are faulty or leaking fluorine
Use the remote control to judge: (This judgment method is applicable to the original gray remote control)
After pressing the rightmost button of the remote control battery for a second, the remote control displays 00, use The temperature
adjustment button can change the displayed number and transmit it to the host through the remote control (as long as the electric control is normal, it can be received and displayed through thelight is displayed), for items with no problem, only the timing light flashes, otherwise both the timing light and the running light flash.
Level diagnostic function
Mainboard
0C The temperature sensor head at room temperature continues to run abnormally
0d The temperature sensor head of the evaporator continues to run abnormally
11 The indoor fan is abnormal and the whole machine stops
12 The main board other The problem continues to run
Detection code 01 Wiring or overheat protector has function block failure
Detection code 04 Wiring error or faulty machine shutdown
Phenomenon 1 The thermal protection is blown
2 The indoor fan is not running normally
Article Url:https://www.liaochihuo.com/info/656367.html
Label group:[sensor] [fuse] [Midea Air Conditioner] [Evaporator]